📘 Transformer OC & SC Tests – Complete Explanation
Open Circuit (OC) and Short Circuit (SC) tests are used to determine transformer parameters without loading it fully. Very important for GATE numericals.
🔹 1. Open Circuit Test (OC Test)
Purpose:- Find core loss
- Find Rc and Xm
- V₀ – Applied voltage
- I₀ – No-load current
- W₀ – Power input
P_core = W₀
Power factor:cosφ₀ = W₀ / (V₀ I₀)
Calculate: I_c = I₀ cosφ₀ I_m = I₀ sinφ₀ Then:Rc = V₀ / I_c Xm = V₀ / I_m
🔹 2. Short Circuit Test (SC Test)
Purpose:- Find copper loss
- Find R_eq and X_eq
- V_sc – Applied voltage
- I_sc – Current
- W_sc – Power
P_cu = W_sc
Equivalent impedance:Z_eq = V_sc / I_sc
Equivalent resistance:R_eq = W_sc / I_sc²
Equivalent reactance:X_eq = √(Z_eq² − R_eq²)
🔹 3. Example
OC Test Data: V₀ = 200 V I₀ = 2 A W₀ = 150 W Core loss:P_core = 150 W
SC Test Data: V_sc = 20 V I_sc = 10 A W_sc = 100 W Equivalent impedance:Z_eq = 20 / 10 = 2 Ω
Equivalent resistance:R_eq = 100 / (10²) = 1 Ω
Equivalent reactance:X_eq = √(2² − 1²) = √3 = 1.73 Ω
🎯 GATE Important Points
- OC test gives core loss
- SC test gives copper loss
- SC voltage very small (5–10% rated)
- Use these parameters for regulation & efficiency
OC Test → Core Loss SC Test → Copper Loss