๐Ÿ“˜ Power Systems – Mega Revision Formula Sheet (Page 20)

Final rapid revision formulas for GATE + PSU.


๐Ÿ”น Per Unit System

Base Current: I_base = S_base / (√3 V_base) Base Impedance: Z_base = V_base² / S_base Per Unit Value: PU = Actual / Base

๐Ÿ”น Fault Analysis

3-Phase Fault Current: I_f = V / Z_total SLG Fault Current: I_f = 3V / (Z1 + Z2 + Z0) Fault MVA: MVA_fault = √3 V I If impedance reduces by x%, fault current increases by 1/(1-x)

๐Ÿ”น Transmission Lines

Surge Impedance: Z_s = √(L/C) SIL = V² / Z_s Short line → Ignore capacitance Medium line → Nominal ฯ€ Long line → Hyperbolic equations

๐Ÿ”น Stability

Power Equation (SMIB): P = (EV/X) sinฮด Maximum Power: P_max = EV / X Swing Equation: M d²ฮด/dt² = P_m - P_e Maximum power at ฮด = 90°

๐Ÿ”น Economic Dispatch

Incremental Cost: dC/dP = ฮป With Losses: (dC/dP) × Penalty Factor = ฮป Penalty Factor: 1 / (1 - ∂P_L/∂P_i)

๐Ÿ”น Load Flow

Gauss-Seidel → Linear convergence Newton-Raphson → Quadratic convergence Slack Bus → V & angle fixed PV Bus → P & V fixed PQ Bus → P & Q specified

๐Ÿ”น HVDC

Power = V × I Advantages:
  • No reactive power flow
  • No stability limit
  • Lower losses for long distance

๐Ÿ”น Protection

Distance Relay → Measures impedance Zone 1 → 80% line Differential Relay → Based on KCL PSM = Fault Current / Relay Setting

๐Ÿ”น Load Factors

Load Factor = Average Load / Peak Load Diversity Factor = Sum of Individual Max / System Max

Page 20 – Mega Revision Formula Sheet Completed

๐Ÿ”ฅ Power Systems Complete Master Module (20 Pages) Achieved ๐Ÿ”ฅ