📘 Advanced Multi-Source Relay Coordination – Hard Numerical
Two generators feed a common bus through two feeders. Overcurrent relays are installed at both feeders and at outgoing line. Design proper relay coordination.
🔹 Given Data
- Fault at end of outgoing feeder = 5000 A
- Generator 1 contribution = 3000 A
- Generator 2 contribution = 2000 A
- CT ratio = 600/5
- Plug setting = 100%
- Coordination Time Interval (CTI) = 0.3 sec
- IEC Standard Inverse Curve
T = TMS × (0.14 / (PSM0.02 − 1))
🔹 Step 1: Pickup Current
Secondary pickup = 5 A Primary pickup = 5 × (600/5) = 600 APickup Current = 600 A
🔹 Step 2: Outgoing Feeder Relay (R1)
Total fault current = 5000 APSM₁ = 5000 / 600 = 8.33
Calculate: 8.330.02 ≈ 1.044Constant = 0.14 / (1.044 − 1) = 0.14 / 0.044 ≈ 3.18
Assume fast clearing time = 0.4 sec0.4 = 3.18 × TMS₁ TMS₁ = 0.4 / 3.18 = 0.126
TMS₁ ≈ 0.13
🔹 Step 3: Generator Relays R2 & R3
Generator 1 Fault Current = 3000 APSM₂ = 3000 / 600 = 5
50.02 ≈ 1.032Constant = 0.14 / 0.032 ≈ 4.375
R2 must operate slower than R1 by CTI: Required time: 0.4 + 0.3 = 0.7 sec0.7 = 4.375 × TMS₂ TMS₂ = 0.7 / 4.375 = 0.16
TMS₂ ≈ 0.16
Generator 2 Fault Current = 2000 A
PSM₃ = 2000 / 600 = 3.33
3.330.02 ≈ 1.025Constant = 0.14 / 0.025 = 5.6
Required time = 0.7 sec0.7 = 5.6 × TMS₃ TMS₃ = 0.7 / 5.6 = 0.125
TMS₃ ≈ 0.13
📊 Final Relay Settings
| Relay | Fault Contribution | TMS | Operating Time |
|---|---|---|---|
| R1 (Feeder) | 5000 A | 0.13 | 0.4 sec |
| R2 (Gen 1) | 3000 A | 0.16 | 0.7 sec |
| R3 (Gen 2) | 2000 A | 0.13 | 0.7 sec |
🎯 Important Concepts
- Multi-source systems require contribution-based coordination
- Each relay sees different fault current
- Coordination interval must be maintained
- PSM differs for each source
Multi-Source Protection = Intelligent Time Grading
No comments:
Post a Comment