📘 Power Systems – Mega Mixed Test (Page 12)

🔹 Section A: MCQ (Concept + Numerical)

Q1. Base impedance at 11 kV, 100 MVA is:
A) 1.21 Ω
B) 12.1 Ω
C) 0.121 Ω
D) 121 Ω

Answer: A) 1.21 Ω

Q2. Ferranti effect is due to:
A) Resistance
B) Inductance
C) Capacitance
D) Frequency

Answer: C) Capacitance

Q3. Fault current increases when:
A) Impedance increases
B) Voltage decreases
C) Impedance decreases
D) Frequency decreases

Answer: C) Impedance decreases

Q4. For SLG fault, sequence networks connected in:
A) Parallel
B) Series
C) Only positive
D) Only zero

Answer: B) Series

Q5. Maximum power transfer occurs at:
A) 60°
B) 45°
C) 90°
D) 120°

Answer: C) 90°


🔹 Section B: Numerical Problems

Q6. A 132 kV system has short circuit current 15 kA. Find fault MVA.

Fault MVA = √3 × V × I = 1.732 × 132 × 15 = 3429 MVA (approx)


Q7. Two generators have incremental costs: dC1/dP1 = 0.04P1 + 5 dC2/dP2 = 0.06P2 + 4 Total load = 200 MW. Find economic load sharing.

Set equal: 0.04P1 + 5 = 0.06P2 + 4 P1 + P2 = 200 Solve: 0.04P1 - 0.06P2 = -1 Multiply by 100: 4P1 - 6P2 = -100 Substitute P1 = 200 - P2: 4(200 - P2) - 6P2 = -100 800 - 4P2 - 6P2 = -100 800 - 10P2 = -100 10P2 = 900 P2 = 90 MW P1 = 110 MW


Q8. Generator reactance = 0.25 pu. Find 3-phase fault current.

I = 1 / 0.25 = 4 pu


Q9. HVDC line ±400 kV carries 1500 A. Find transmitted power.

P = V × I = 400,000 × 1500 = 600 MW


Q10. If system frequency drops from 50 Hz to 49.8 Hz, find % frequency deviation.

Deviation = (0.2 / 50) × 100 = 0.4%


🔹 Section C: Quick Revision Checklist

  • Per Unit System basics
  • Transmission line effects
  • Symmetrical & Unsymmetrical faults
  • Stability power angle
  • Economic dispatch
  • LFC & AVR
  • HVDC & FACTS
  • Protection coordination

Power Systems Question Bank Series Completed (Page 1–12)